Specifications:


Dimensions
  • Monitoring System – 7.5”w x 12”d x 3.5”h
Power Supply Requirements
  • 120v to 16v plug-in transformer, included -or-
  • 12v DC from generator -or-
  • 24v DC from generator
Communication options
  • Analog phone line (installer change dip switch setting to 9 dial for outside line)
  • Internet (Ethernet)
  • Cellular
Communications Features
  • Communication test button
  • LED shows signals stored waiting to send
  • Communication Failure LED
Monitoring Signals
  • Building power
    • Building power not available for two minutes
  • Generator ‘on’
    • Generator power detected for 15 seconds or more
  • No Utility power
    • Utility power not available for 15 seconds or more
  • Generator Fault (requires 2-wire start generator)
    • Detects no generator power or low power within 60 seconds of transfer switch closing
  • Auxiliary inputs - 4, user defined
    • common fault
    • low fuel
    • high temperature
    • Transfer Switch Position
    • other
  • Run time
  • Fail to exercise
  • All signals have time stamp
Remote communication
  • Remote outputs – Two user defined (peak shaving, resetting faults)
    • operated via the customer site page
  • Remote start
    • Operated via the customer site page
Signal notifications
  • Full customization, unlimited notifications
    • e/mail
    • text message
Internet access
  • Dealer: view and edit all customer information, signals
  • Customer View only signal history and information
Documentation
  • Customer e-mail of monthly signal history
  • Customer may view full signal history on the internet